Can I use the ATV660 potentiometer in Hand and Auto?
Issue:
Can the drive be controlled in Hand or Auto only using the Potentiometer on the door?
Product Line:
Altivar Process Drive
Environment:
ALL
Cause:
Programming
Resolution:
You can use only the Potentiometer for speed control.
Go to My Preferences > Access Level and set to Expert
Go to Complete Settings > Command and Reference > Ref Freq Channel 1, change from AI3 to AI1.
Can the drive be controlled in Hand or Auto only using the Potentiometer on the door?
Product Line:
Altivar Process Drive
Environment:
ALL
Cause:
Programming
Resolution:
You can use only the Potentiometer for speed control.
Go to My Preferences > Access Level and set to Expert
Go to Complete Settings > Command and Reference > Ref Freq Channel 1, change from AI3 to AI1.
Released for: Schneider Electric UK