Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Why am I getting internal faults on ATV320 when one speed pot is being used on 2 different ATV320 drives?
Issue:
Getting Internal Faults on ATV320 , when one speed pot is being used on 2 different ATV320 drives

Product Line:
ATV320

Environment:
Speed pot

Cause:
n/a

Resolution:
When using qty of 2- ATV320 drives and was using one speed pot, for both drives. The drives work ok normally, but when you stop one of the drives (and not the other one) - gives a Internal fault. Appears the +10v is being backfed into the other drive. If you stop them at the same time, then works ok.  One solution would be to provide a separate speed pot for each drive or stop them at the same time.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings