How to configure a serial daisy chain to have devices split between multiple I/O Servers in Power SCADA Operation (PSO) 9.0
Issue
Some of the devices on a serial daisy chain need to live on a different I/O Server than the rest of the devices on that daisy chain.
Product Line
Power SCADA Operation 9.0
Environment
Studio, Topology, PSO server
Cause
In PSO, a specific Port cannot be used on more than one I/O Server.
Resolution
To split a daisy chain between multiple I/O Servers, a unique Port is needed for each I/O Server. For example, assume a daisy chain of 10 devices needs 5 serial devices on I/O Server 1, and the other 5 on I/O Server 2. The port for the 5 serial devices on I/O Server 1 is named North_IO1_devices. A second unique port needs to be defined for the devices that will exist on I/O Server 2, perhaps named South_IO2_devices.
Some of the devices on a serial daisy chain need to live on a different I/O Server than the rest of the devices on that daisy chain.
Product Line
Power SCADA Operation 9.0
Environment
Studio, Topology, PSO server
Cause
In PSO, a specific Port cannot be used on more than one I/O Server.
Resolution
To split a daisy chain between multiple I/O Servers, a unique Port is needed for each I/O Server. For example, assume a daisy chain of 10 devices needs 5 serial devices on I/O Server 1, and the other 5 on I/O Server 2. The port for the 5 serial devices on I/O Server 1 is named North_IO1_devices. A second unique port needs to be defined for the devices that will exist on I/O Server 2, perhaps named South_IO2_devices.
- This port can be created for I/O Server 2 in the Ports table located in Topology > Components and Mapping. The IP address will be the same for both ports since it is the same gateway device/daisy chain.
- Once the Port is created, Navigate to Topology > IO Devices. Assign the newly created port to the desired devices for I/O Server 2, and change the I/O Server fetid for each device to the appropriate name.
- Save and compile the project.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.