Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
why does Control expert generate a linking error when I link a variable from a PROCESS section to a variable from a SAFE section ?
This error occurs when the client :
  • uses Control Expert 14.0
  • loads an already-built application
  • adds new variables in a SAFE section and in a SAFE section
  • links the variables
  • run a "build change"

workarounds :
  • export to .zef format, and reimport
  • run a build-all instead of a build-change

This bug was fixed in Control Expert 14.1

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings