How can we help you today?

Why does Control Expert v14.0 generate a linking error when linking a PROCESS section variable to a SAFE section variable?

This error occurs when the customer:

  • uses Control Expert 14.0
  • loads an already-built application
  • adds new variables in a Process section and in a SAFE section
  • links the variables
  • run a "build change"


Possible workarounds :

  • export to .zef format, and reimport
  • run a build-all instead of a build-change


This bug was fixed in Control Expert 14.1

Schneider Electric UK

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.