How can we help you today?
Can I used the Altivar Process Drive to power up a step down transformer?
Issue:
Is it ok to connect output of the Altivar Process Drive to a step down transformer?
Product Line:
Altivar Process Drive
Environment:
All model numbers, all serial numbers
Cause:
Customer wanted to use the drive as a step down transformer from 460V to 230V
Resolution:
No, Altivar Process Drives are designed to run inverter-duty motors, and are not recommended to have a transformer, at the output.
Is it ok to connect output of the Altivar Process Drive to a step down transformer?
Product Line:
Altivar Process Drive
Environment:
All model numbers, all serial numbers
Cause:
Customer wanted to use the drive as a step down transformer from 460V to 230V
Resolution:
No, Altivar Process Drives are designed to run inverter-duty motors, and are not recommended to have a transformer, at the output.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.