The ATV320 is showing STO on the screen?

Issue:
ATV320 STO status on screen.

Product line:
Altivar 320

Resolution:
On the terminal block, look for P24. There must be a jumper between P24-STO.
Without this jumper the drive will display STO on the screen and will not be able to run.