How can we help you today?

PME maintenance tasks fail with error 0x1F4 if IONMaintenance user is not added to the Administrators group

Issue
PME maintenance tasks fail with error 0x1F4 if IONMaintenance user is not added to the Administrators group

In the  SQL Error logs, you may see the following error
"Login failed for user 'ServerName\IONMaintenance'. Reason: Failed to open the explicitly specified database 'ION_Network'. [CLIENT: <local machine>]"

Error message

Facts

  • If IONMaintenance user is added to windows administrator group, the tasks run successfully
  • IONMaintenance user roles are correctly set up in SQL for the 4 PME databases
  • IONMaintenance user has full write access to the  Backup destination folder
  • IONMaintenance is a member of "Users" group



Product Line
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023

Power Monitoring Expert 2024

Environment
PME Standalone systems

Cause
The privileges granted to the group BUILTIN\Users has higher priority over User privileges.

Resolution
In SQL, grant "db_backupoperator", "db_ddladmin" and "Maintenance" Membership for "BUILTIN\Users" for all PME databases


ION Maintenance Privileges

User permissions


Schneider Electric UK

Explore more

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more

Explore more

Need help?

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Find support resources for all your needs, in one place.