How to update the RTC of the HMIST6 using a M172

Software

EcoStruxure Operator Terminal Expert V3.5 SP1

Product Line

Harmony HMIST6
Modicon M172P

Explanation

The Modicon M172P has a defined memory space for the time management in the folder "System Clock Values".
The variables from %MW8736 up to %MW8743 are for reading the actual date and time of the controller and the variables from %MW8744 up to %MW8751 are to setting the date and time.
The variable "sysClockSet_Upload" in the M172 allows us to update the RTC in the controller when we have configured the variables %MW8744 to %MW8750.
Those variables must be link to our Harmony HMI in the EcoStruxure Operator Terminal Expert, in a global script we can write the Date and time of our HMI using the actual values of the PLC.
The example is attached in this FAQ.

Schneider Electric UK

Attachment(s)
EOTE_HMIST6_M172_SysClock_rev0.0.vxdz [169.83 KB]