How is calculated the processor load value in the BMXNOC0401 communication module?
Issue:
How is calculated the Processor load value in the BMXNOC0401 communication module?

Product Line:
M340
BMXNOC0401

Environment:
Web page

Resolution:
Processor load value is a ratio between “CPU non-Idle tasks Time” and “Total CPU time”( if idle is 30% then CPU utilization is 100-30=70%).
The CPU is a multi-task system, the execution order of the different type of tasks depend on their priorities .
In the case of the BMXNOC0401, the following tasks have an impact on its load :
  • Server and client traffic packets per second as each packet is inspected and a transaction occurs
  • Size of I/O scanner image: bigger the scanner load, the longer it takes to copy from the xbus
  • PLC CPU scan time, as we have to transfer the I/O scanner twice a scan cycle.
  • General network traffic like multicast and broadcast traffic as it must be inspected

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings