Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

1.Issue

How to know the absence of x80 IO in local M580 rack when it is configured as Device DDT ?

2.Environment

M580 series ,X80

3.Resolution

The detail diagnostics status of x80 IO could be accessed by implementing READ_STS_MX.
Here are two samples to get status for digital and analog modules.


When COM_FLT is set to 1 ,it means the module could not be detected by CPU and module would be absent in the rack.

Schneider Electric UK

Attachment(s)
read_sts.zip [54.48 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings