How can we help you today?
Why the BMXAMI0810 only reports MOD_ERROR in the IODDT?
Why the BMXAMI0810 only reports MOD_ERROR in the IODDT T_GEN_MOD?
N/A When any channel comes across brokenWire,upperOvr,lowerOv,spiError,or HARDWARE_SELF_TEST_FAULT, the MOD_ERROR will be activated. In special when the channel
has problems, the CH_ERROR will be activated also.
If there is only MOD_ERROR in the IODDT, customer has to verify the upper overflow or lower overflow.
N/A When any channel comes across brokenWire,upperOvr,lowerOv,spiError,or HARDWARE_SELF_TEST_FAULT, the MOD_ERROR will be activated. In special when the channel
has problems, the CH_ERROR will be activated also.
If there is only MOD_ERROR in the IODDT, customer has to verify the upper overflow or lower overflow.
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.