Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Are the iC60H miniature circuit breakers suitable for use on a DC system?

Yes
The standard iC60H miniature circuit breakers are suitable for use on DC systems IEC/EN 60947-2.

1 pole 48Vdc 20kA
1 pole 72Vdc 10kA
2 pole 133Vdc 10kA (in series)
3 pole 133Vdc 20kA (in series)
4 pole 250Vdc 10kA ( in series )

However we also manufacture a specific range of C60-DC ( A9N*** ) suitable for use on a DC system which has a higher performance.

1 pole 220Vdc 10kA
2 pole 250Vdc 20kA
2 pole 440Vdc 10kA
2 pole 500Vdc 6kA

Schneider Electric UK

Attachment(s)
C60H DC Data Sheet.pdf [705.64 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings