Data Center Expert | Devices Stuck in Maintenance Mode After Upgrade to 7.8.1

Issue:
After upgrading to Data Center Expert version 7.8.1, devices are stuck in maintenance mode.

Product line:
StruxureWare Data Center Expert (DCE)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)

Environment:
StruxureWare Data Center Expert (7.8.1)

Resolution:

In order to remove the device from maintenance mode, the device must first be entered into maintenance mode again.

1) Within the DCE Desktop Client, navigate to the Monitoring perspective:
ddce icons

2) Click on All Devices or the specific device group within the Device Groups pane that contains the device stuck in maintenance mode:
dce all devices

3) Within the Device View pane, right-click on the device stuck in maintenance mode and select Enter Maintenance Mode:
dce device view

4) Leave the default value of Now for Enter maintenance mode and Never for Exit maintenance mode and click OK:
dce main t mode

5) Right-click on the device stuck in maintenance mode and select Exit Maintenance Mode:
dce exit maint mode

6) Click OK to Exit Maintenance Mode for the device.
dce exit maint mode

The device should now have exited maintenance mode.  If it did not, please reach out to your local technical support for assistance.

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center