How to do tighten to the correct Torque for Acti9 Products - Video

Below is a video showing how to apply the torque correctly to Acti9 products:




The table below details the Torque requirements for the majority of the Acti9 product range:
RangeTypeTightening Torque
iC60H Circuit Breaker1 to 25 A2 Nm
iC60H Circuit Breaker32 to 63 A3.5 Nm
iC60H RCBON in and L in3.5 Nm
iC60H RCBOL out and N out2 Nm
Vigi iC60 add-on RCD25 A2 Nm
Vigi iC60 add-on RCD40 to 63A3.5 Nm
iID RCCBiID3.5 Nm
Electrical auxiliaries for
iC60, iID, iDPN Vigi, RCA and ARA
Indication auxiliaries1 Nm
Electrical auxiliaries for
iC60, iID, iDPN Vigi, RCA and ARA
Tripping auxiliaries1 Nm
Accessories for
iC60, iID, iDPN Vigi, Reflex iC60, RCA, ARA, iSW
Multi-cable terminal2 Nm
Accessories for
iC60, iID, iDPN Vigi, Reflex iC60, RCA, ARA, iSW
50 mm² terminal Al10 Nm
Accessories for
iC60, iID, iDPN Vigi, Reflex iC60, RCA, ARA, iSW
Screw-on connection for ring terminal2 Nm
iDPN circuit breakersDT40, i DPN, C402 Nm
iDPN circuit breakersDT603.5 Nm
iDPN Vigi RCD4 to 40 A2 Nm
iC120H circuit breakers63 to 125 A3.5 Nm
Vigi iC120 add-on RCDVigi C1203.5 Nm
Accessories for
iC120, DPN, DPN Vigi, C60H-DC, SW60-DC, C60NA-DC, C60PV-DC, iSW devices
Multi-cable terminal2 Nm
Accessories for
iC120, DPN, DPN Vigi, C60H-DC, SW60-DC, C60NA-DC, C60PV-DC, iSW devices
50 mm² Al terminal10 Nm
Accessories for
iC120, DPN, DPN Vigi, C60H-DC, SW60-DC, C60NA-DC, C60PV-DC, iSW devices
Screw-on connection for ring terminal2 Nm
Electrical auxiliaries for
iC120, DPN, DPN Vigi, ID, C60H-DC, SW60-DC, C60PV-DC, C60NA-DC devices
Indication and tripping auxiliaries1 Nm
P25M Load protection Motor starter protectionP25M1.7 Nm
P25M Load protection Motor starter protectionElectrical auxiliaries1.4 Nm
iPRD surge arrestersiPRD3.5 Nm
iQuick PRD Withdrawable surge arresteriQuickPRD2.5 Nm
iPRD-DC surge arrestersiPRD-DC2 Nm
REDs, REDtest Earth leakage protection Automatic recloserREDs, REDtest N, L2 Nm
REDs, REDtest Earth leakage protection Automatic recloserREDs, REDtest Aux0.4 Nm
RED A type 30mA Earth leakage protection Automatic recloserRED A type 30 mA 25 to 40A2 Nm
Reflex iC60H Control, remote control Integrated control circuit breakersPower Connection 10 to 25 A2 Nm
Reflex iC60H Control, remote control Integrated control circuit breakersPower Connection 40 to 63A3.5 Nm
Reflex iC60H Control, remote control Integrated control circuit breakersPower supply (N/P) & Inputs (Y1/Y2)1 Nm
Reflex iC60H Control, remote control Integrated control circuit breakersOutputs (O/C, auto/OFF)0.7 Nm
ARA automatic reclosers For iC60 CB and iID RCCBPower supply (N/P) & Inputs (Y1/Y2)1 Nm
ARA automatic reclosers For iC60 CB and iID RCCBOutputs (OF/Locked)0.7 Nm
RCA remote controls For iC60 CBPower supply (N/P) & Inputs (Y1/Y2)1 Nm
RCA remote controls For iC60 CBOutputs (OF)0.7 Nm
Acti 9 smartlinkAnalog connector0.8 Nm
Acti 9 smartlinkPower supply connector0.8 Nm
Acti 9 smartlinkModbus connector0.8 Nm
iCT contactorsiCT Control Circuit0.8 Nm
iCT contactorsiCT Power Circuit 16 and 25 A0.8 Nm
iCT contactorsiCT Power Circuit 40 to 63 and 100 A3.5 Nm
iCT contactors iACTs, iACTp, iACTc, iATEt 0.8 Nm
iCT contactorsiACT24 Power supply (N/P) & Input (Y1/Y2)1 Nm
iTL impulse relaysiTL, iTLi, iTLc, iTLm, iTLs, iETL 16 A Power and Control1 Nm
iTL impulse relaysiTL, iETL 32 A Control1 Nm
iTL impulse relaysiTL, iETL 32 A Power1.2 Nm
iTL impulse relaysiATLs, iATLc, iATLc+s, iATLc+c, iATLm, iATEt, iATL4, iATLz1 Nm
iTL impulse relaysATL24 Power supply (N/P) & Inputs (Y1/Y2)1 Nm
iTL+ high-performance impulse relaysTL+1 Nm
iIL indicator lightsiIL1 Nm
iPB pushbuttonsiPB1 Nm
iSW switchesiSW 40 to 125 A3.5 Nm
iSW switchesiCF1 Nm
iSW switchesiSW 22 and 32 A1.2 Nm
iSW switchesOF iSW1.2 Nm
iSSW linear switchesiSSW1 Nm
iTR transformersiTR0.5 Nm
iSO bells and iRO buzzersiSO1.3 Nm
STI isolatable fuse carriersSTI2 Nm
SBI fuse holder with indicator light14 x 51 mm & 22 x 58 mm3.5 Nm
DIN rail selector switches iCMB, iCMD, iCME, iCMC, iCMV and iCMAiCMB, iCMD, iCME, iCMC, iCMV and iCMA0.35 Nm
Timers MIN, MINs, MINp and MINtMIN, MINs, MINp, MINt1.2 Nm
Time switches IHP, IH, IHH and ITAIHP, IH, IHH and ITA1.2 Nm
Twilight switches IC100, IC2000P+IC100, IC2000P+1.2 Nm

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center