Is it possible to reset the TM3BC Bus Coupler?

We can perform a factory reset to the Bus Coupler (TM3BCEIP, TM3BCSL , TM3BCCO) if we follow the next steps:
STEPAction
1Remove power from the bus coupler.
2Disconnect all communication cables.
3Set the two rotary switches to position 8 (arrows down).
4Apply power to the bus coupler.
5Wait for a minimum of 30 seconds.
6Set the two rotary switches to position 0 (arrows up).
7Remove power from the bus coupler.
8Apply power to the bus coupler.

If we are not able to connect via USB please check the Rotary Switch position not to be in 00, 128, 129 (TM3BCSL or TM3BCCO).

Remember: Any modification of the rotary switch position is taken into account after power up.