What are the improvements from Series 300 Group 1 to Group G controller?

Series 300 Automatic Transfer Switch Group 1 to Group G control improvements.

image.png
Controller Group Improvements from Group 1 to Group G
FeaturesGroup 1 Group G
Membrane Panel (HMI)Flush-mounted control and display panel with LED indicator for switch position and source availability.128x64 graphical LCD Display with switch position, source availability, common alarm and Not-In-Auto LED indicator.
HMI control buttonstactile keystactile keys
Supported Transition TypeOpen Transition OnlyOpen Transition and Delayed Transition
Nominal UnitsVia DipswitchVia Dipswitch
Phase Selection1 Ø or 3 Ø1 Ø or 3 Ø
Frequency50 or 60 Hz50 or 60 Hz
Voltage and Frequency Settings Setting AdjustmentsVia DipswitchVia Dipswitch
Pick up Normal Source Voltage90% or 95%85 to 100%
Drop out Normal Source Voltage70% to 90%70 to 98%
Pick up Emergency Source Voltage90% Fixed85 to 100%
Drop out Emergency Source Voltage75% Fixed70 to 98%
Pick up Emergency Source Frequency95% Fixed86 to 100%
Drop out Emergency Source Frequency85% Fixed85 to 98%
Normal Over Voltage TripN/A102 to 115% (*default set to off)
Emergency Over Voltage TripN/A102 to 115% (*default set to off)
Normal Over Frequency TripN/A101 to 110% (*default set to off)
Emergency Over Frequency TripN/A101 to 110% (*default set to off)
Pick up Normal Source FrequencyN/A86 to 100%
Drop out Normal Source FrequencyN/A85 to 98%
Normal & Emergency Voltage UnbalanceN/AN/A
Pick up Normal Voltage UnbalancedN/A3-18%
Drop out Normal Voltage UnbalancedN/A5-20%
Time Delay Settings Setting AdjustmentsVia Dip Switch (DS)/Potentiometer (P1/P2)Via built-in Membrane Controls with LCD Display
Override Normal Source Momentary Outage1 or 3 Seconds - DS0 to 6 Seconds
(Can be extended from 0-60 min 59 secs.via external 24VDC through optoinal REX Module/18RX)
Transfer to Emergency0 to 5 Minutes - P20 to 60 Minutes 59 Seconds
Re-transfer to Normal Utility Power Loss Mode1 Sec. to 30 Mins. - P10 to 60 Minutes 59 Seconds
Engine Cool Down5 Minutes - Fixed0 to 60 Minutes 59 Seconds
Override Emergency Source Momentary Outage4 Seconds - Fixed0 to 6 Seconds
In-phase Transfer Timer1.5 Secs0 to 3 secs
Built-in Emergency ExerciserWeekly, 20 min. run duration - Fixed - DSWeekly or Bi-Weekly (20 min. run duration)
Programmable Emergency Exerciserwith Optional Accessory 11BG
Weekly/ Bi-Weekly
Run Duration(0- 23h : 59 min.)
with Optional Accessory 11BE
All, Alt, 1st, 2nd, 3rd, 4th, 5th day or the week
Run Duration(0- 23h : 59 min.)
Number of Independent Programs with Programmable Emergency Exerciser1 program only7 independent programs
Indication and Controls
Control Type
Via separate Membrane ControlsVia built-in Membrane Controls with LCD Display
Load Connected to NormalYesYes
Load Connected to EmergencyYesYes
Normal Source AvailableYesYes
Emergency Source AvailableYesYes
Transfer Test SwitchYesYes
By-pass Time DelayYesYes
In-Phase MonitorYesYes
Load Disconnect Contacts with Time DelayStd. (3, 10 , 20 sec. adjustable delays) - DSStd. (0-5 min. 59 sec. adjustable delays)
Event LogN/AOptional (with Acc. 11BE)
Current Measurement CapabilityN/AOptional (with Acc. 23GA/23GB)
Load Shed CapabilityN/AOptional (with Acc.30A or 30B*)
128*64 Graphical LCD DisplayN/AYes
128*64 Graphical LCD Display multiple language capabilityN/AYes
Transfer Operating modeOpen Transition onlyOpen or delayed transition
Commit to TransferYes - Fixed Enabled/Disabled - Can be adjusted
Pre-mounted Power Meter on load side with CTN/AYes - with optional 135L
Event LoggingN/AYes - (with optional 11BE)
System StatusN/AYes (Via LCD Display)
Self DiagnosticsN/AYes (Via LCD Display)
Statistics And DiagnosticsN/AVia built-in Membrane Controls with LCD Display
Total TransferN/AYes
Total Transfers Due To Source FailuresN/AYes
Days EnergizedN/AYes
Total Time N AvailableN/AYes
Total Time E AvailableN/AYes
Input And Output StatusN/AYes
Accessories/Options*

Note* - These are not standard but list of optional features that can be added on a Transfer Switch using a certain Controller Group. It needs to be specified in the Transfer Switch Catalog upon ordering.

11BG Programmable Exerciser control board with 2-line LCD Display and Source Availbility Contacts.
44A/44G Strip Heater
72E Communication Module

11BE Feature Bundle: 7  independent Exerciser programs, RS485 enable, Common Alarms, Event Logs Access
18RX Relay Expansion Module
44A/44G Strip Heater
72EE Communication Module
23GA/23GB Current Sensing Module
1 UP Uninterruptible Power Supply Module
73 Surge Protection Device option
62W Audible Alarm
135L Digital Power Meter- Load side

For further questions, you may send your inquiry to customercare@ascopower.com or Contact 1.800.800.ASCO (2726)

Schneider Electric UK

Attachment(s)
ASCO-SERIES-300-Group-G-Upgrade-Pub-2002-FINAL-lo-res.pdf [238.85 KB]
G1 and GG Comparison Features 2 of 2.png [118.45 KB]
G1 and GG Comparison Features 1 of 2.png [174.65 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings