How does one connect an HMI to Modicon M172 or M172 HVAC PLC for Modbus Serial communication?
Issue
How does one connect an HMI to Modicon M171 or M172 HVAC PLC for Modbus Serial communication?
What are the part numbers for the connectors on these PLCs?
Product Line
Modicon M171, M172 HVAC PLCs
EcoStruxure Machine Expert HVAC
Environment
Connectors for Serial communications
Resolution
The Serial connectors on Modicon M171 and M172 require a terminal block that have screw-type connectors for bare wire.
These kits are sold separately and are specific to the number of I/O pins on the corresponding model of PLC:
For the 14 I/O M171 or M172 model:
Part Number: TM171ASCTB14
For the 27I/O M171 or M172 model:
Part Number: TM171ASCTB27
The connectors attach to this port on the PLC:
In order to connect an HMI, you would obtain the Serial Connector pinout diagram from the specific HMI's Hardware Manual, then wire the connectors accordingly.
See this example with the HMISTO715:
On the HMISTO715, the pinout is as follows:
So a cable with an RJ45 connector would have to be manually spliced from:
HMI M171/M172
4 D1 ----------------- “+”
5 D0 ------------------ “-“
8 SG ------------------ “GS”
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.