How can we help you today?

How do I change the "Installer" account password for the BMENUA0100 OPC UA module?

Issue:
How to change the password for the BMENUA0100 OPC UA module Installer account


Product Line:
BMENUA0100, EcoStruxure Control Expert

Resolution:
The installer password can be changed. However the module must be in the standard mode by setting the rotary switch located at the back of the module.  Once in standard mode, log into the module via your browser using the default user name and password. once connected, you will see "Installer" in green in the top right corner of the browser. click on it, and you will see the option to change password.
installer

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings