How can we help you today?

What is the installation procedure as how to mount the TeSys Giga contactor without cable memory on a circuit breaker ?

TeSys Giga contactor can be installed directly to NSX circuit breakers, by aligning their terminal depth with dedicated cable memory kits.

image.png

Note: TeSys Giga advanced version contactors are always delivered with cable memory kits pre-installed (LA9G310●/ LA9G410●). The existing cable memory kit to be replaced with alternative cable memory kits (LA9G311●/ LA9G411●). when installing in alignment to NSX breaker main power terminals.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center