Can you use both Level control and booster control on the ATV630 at the same time?
Issue:
Customer wants to use both Booster and level control at the same time
Product Line:
ATV630
Environment:
All
Cause:
When level control is selected, Booster control is not allowing programming.
Resolution:
The level control and booster control are applications and not functions. So depending on the application selected via the macro APPT some parameter will be locked. For example if you select Pump booster control (APPT=Boost) the parameters of the other application will be locked for example: LCM (Level Control Mode) will be deactivated.
So no it is not possible to use the booster control and the level control at the same time.
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.