Control Expert 15 returns error 'mfc140u.dll is missing' when starting

Control Expert returns the error 'system error: mfc140u.dll is missing' when trying to start.

This error will occur if the mfc140u.dll file already exists on the PC and it is of a newer version when Control Expert is installed.  The 'mfc140u.dll' file is part of the 'Microsoft Visual C++ 20xx Redistributable ' libraries that gets installed during the Control Expert installation process.  Per Microsoft rules, a software installation is not allowed to overwrite an existing version of a Microsoft '.dll' with an older version.  This rule prevented the
proper installation of the required  'Microsoft Visual C++ 20xx Redistributable ' libraries.

image.png


The specific version 'mfc140u.dll' file is essential for the registration of other '.dll's that are included with Control Expert.  As a result of this, the error could also be accompanied with the following error:

image.png

To resolve the issue,
  • Rename the existing .'mfc140u.dll' file.
  • Uninstall Control Expert.
  • Reboot the PC.
  • Reinstall Control Expert.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center