HEP meter v3.1.0 firmware FAQ: Fiber Ethernet and 4-wire modules
Issue
Questions about the V3.1.0 Firmware for ION900, PM8000 and ION7400 meters
Product
ION9000
PM8000
ION7400
Resolution
Upgrades
Q: Where can I find the firmware to upgrade my meter's firmware
A: Go to se.com, search for "v3.1.0 Firmware and Associated Files". Select the files for the meter type you are interested in and download zip file.
Q: How do I calculate the SHA-256 File Signature?
A: Please refer to https://www.se.com/ww/en/faqs/FA414544/ for different ways to calculate the file signature.
Q: What software can I used to upgrade my meter(s)?
A: ION Setup
Q: What version of ION Setup can be used to upgrade a meter to V3.1.0 firmware?
A: Recommend using the latest version of ION Setup, here.
Q: What is the minimum version of firmware needed to upgrade a meter to V3.1.0?
A: V2.1.0
Q: Can I downgrade the firmware after upgrading my meter?
A: Meters with V3.1.0 Firmware can be downgraded to V3.0.0 firmware only. Cannot downgrade a meter below V3.0.0.
Q: Do I need to update the display firmware?
A: No new display firmware required when upgrading a meter from V3.0.0
Q: Does upgrading the meter remove onboard logs?
A: Yes, upgrading a meter will reset onboard logs. Be sure any desired logged information is stored outside the meter before upgrading the firmware.
Q: Does V3.1.0 correct modbus exceptions when one or more registers has N/A value?
A: Yes, V3.1.0 firmware is the recommended fix for V3.0.0 meters with this behavior.
Option Modules
Q: What new option modules are supported with V3.1.0 Firmware?
A: Fiber Ethernet and 4-wire serial option modules
Q: Does the meter support multiple 4-wire option modules?
A: No the meter supports a single 4-wire option module
Q: Does the meter support multiple fiber option modules?
A: No the meter supports a single fiber option module
Q: What happens if more than 1 fiber or 4-wire option modules are connected to a meter?
A: Fiber and 4-wire modules will show a solid red LED and IO modules will show a flashing red LED. All modules connected to the meter will become deactivated. An error will be reported in the onboard event log. ION Setup will display a persistent warning message until the unsupported configuration is corrected by the user
Q: When connecting 4-wire option module to meter, can I still use onboard com port(s)
A: For the ION7400 and PM8000, there is only 1 onboard com port, this port is replaced when 4-wire module connected. For ION9000, com port 2 can still be used, com 1 is replaced with the 4-wire option modules.
Q: What IEC61850 ICD file should I use for a meter with 4-wire and Fiber option cards.
A: Refer to the text document included with ICD files for more information. 4-wire and fiber option cards do not have a specific ICD version Only the digital and analog option modules connected to a meter determine what ICD file to use.
Templates\Frameworks
Q: Is there a new template\framework with the new firmware?
A: Yes the new template is included with the firmware install files.
Q: Where can I find the .dcf file for my meter
A: Template files are included with the firmware files from se.com
Q: Where is the MID template?
A: Standard and MID templates have been combined.
Q: Can V2.2.0 Templates be pasted on meters with V3.1.0 firmware
A: Yes meters are backwards compatible with older templates. Any changes with V3.0.0 templates are not included when pasting older templates.
Q: What changes to the template were made for WELMEC compliance?
A: “Pwr Up” Setpoint logic changed to generate an alarm on meter's display when meter first powers up.
COMTRADE
Q: What changes were made to COMTRADE files?
A: Zero padding added to COMTRADE file timestamps
Questions about the V3.1.0 Firmware for ION900, PM8000 and ION7400 meters
Product
ION9000
PM8000
ION7400
Resolution
Upgrades
Q: Where can I find the firmware to upgrade my meter's firmware
A: Go to se.com, search for "v3.1.0 Firmware and Associated Files". Select the files for the meter type you are interested in and download zip file.
Q: How do I calculate the SHA-256 File Signature?
A: Please refer to https://www.se.com/ww/en/faqs/FA414544/ for different ways to calculate the file signature.
Q: What software can I used to upgrade my meter(s)?
A: ION Setup
Q: What version of ION Setup can be used to upgrade a meter to V3.1.0 firmware?
A: Recommend using the latest version of ION Setup, here.
Q: What is the minimum version of firmware needed to upgrade a meter to V3.1.0?
A: V2.1.0
Q: Can I downgrade the firmware after upgrading my meter?
A: Meters with V3.1.0 Firmware can be downgraded to V3.0.0 firmware only. Cannot downgrade a meter below V3.0.0.
Q: Do I need to update the display firmware?
A: No new display firmware required when upgrading a meter from V3.0.0
Q: Does upgrading the meter remove onboard logs?
A: Yes, upgrading a meter will reset onboard logs. Be sure any desired logged information is stored outside the meter before upgrading the firmware.
Q: Does V3.1.0 correct modbus exceptions when one or more registers has N/A value?
A: Yes, V3.1.0 firmware is the recommended fix for V3.0.0 meters with this behavior.
Option Modules
Q: What new option modules are supported with V3.1.0 Firmware?
A: Fiber Ethernet and 4-wire serial option modules
Q: Does the meter support multiple 4-wire option modules?
A: No the meter supports a single 4-wire option module
Q: Does the meter support multiple fiber option modules?
A: No the meter supports a single fiber option module
Q: What happens if more than 1 fiber or 4-wire option modules are connected to a meter?
A: Fiber and 4-wire modules will show a solid red LED and IO modules will show a flashing red LED. All modules connected to the meter will become deactivated. An error will be reported in the onboard event log. ION Setup will display a persistent warning message until the unsupported configuration is corrected by the user
Q: When connecting 4-wire option module to meter, can I still use onboard com port(s)
A: For the ION7400 and PM8000, there is only 1 onboard com port, this port is replaced when 4-wire module connected. For ION9000, com port 2 can still be used, com 1 is replaced with the 4-wire option modules.
Q: What IEC61850 ICD file should I use for a meter with 4-wire and Fiber option cards.
A: Refer to the text document included with ICD files for more information. 4-wire and fiber option cards do not have a specific ICD version Only the digital and analog option modules connected to a meter determine what ICD file to use.
Templates\Frameworks
Q: Is there a new template\framework with the new firmware?
A: Yes the new template is included with the firmware install files.
Q: Where can I find the .dcf file for my meter
A: Template files are included with the firmware files from se.com
Q: Where is the MID template?
A: Standard and MID templates have been combined.
Q: Can V2.2.0 Templates be pasted on meters with V3.1.0 firmware
A: Yes meters are backwards compatible with older templates. Any changes with V3.0.0 templates are not included when pasting older templates.
Q: What changes to the template were made for WELMEC compliance?
A: “Pwr Up” Setpoint logic changed to generate an alarm on meter's display when meter first powers up.
COMTRADE
Q: What changes were made to COMTRADE files?
A: Zero padding added to COMTRADE file timestamps
Released for: Schneider Electric UK
Explore more
Range:
Explore more
Range:
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.