Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What is a USF fault on ATV320

Article available in these languages: Thai

Issue:
USF fault on ATV320

Product Line:
Altivar Machine, ATV320

Environment:
All serial numbers

Cause:
• Supply mains too low
• Transient voltage dip

Resolution:
• Measure incoming line to line voltages
• Check the DC bus voltage on PA and PC
• Check the voltage and the parameters of [UNDERVOLTAGE MGT] (USb-)


ATV320 programming manual:
https://www.se.com/ww/en/download/document/NVE41295/ ​​​​​​​

Schneider Electric UK

Attachment(s)
ATV320_Programming_Manual_EN_NVE41295_03.pdf [2.5 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings