Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
What causes an input phase loss PHF fault on the ATV12?
Issue:
Getting a input phase loss PHF fault on ATV12

Product Line:
Altivar Machine, ATV12

Environment:
All serial numbers


Cause:
• Drive incorrectly supplied or a fuse blown
• Failure of one phase
• 3-phase ATV12 used on a 1-phase line supply
• Unbalanced load
• This protection only operates with the drive on load

Resolution:

• Check the power connection and the fuses.
• Use a 3-phase line supply.
• Disable the fault by setting Input Phase loss detection IPL page 94 = nO.
• Check the motor connection and any isolating devices located between the drive and the motor (contactors, circuit breakers, etc.).


ATV12 user manual:
https://www.se.com/ww/en/download/document/BBV28581/

Schneider Electric UK

Attachment(s)
ATV12_user_manual_EN_BBV28581_04.pdf [3.62 MB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings