Can an Altivar drive be used to create three phase power to supply an entire machine or system?
Issue:
Can the Altivar drive act as a power supply for non-motor loads?
Product Line:
Altivar
Environment:
All models
Cause:
Applications to change power systems
Resolution:
Altivar drives are designed to power motor loads only. It is a misapplication to use the drive output to power other loads, such as a control transformer, relay coils, resistive loads.
Drives can generally convert single phase power to three phase (check ratings) and will vary the output voltage and frequency to control a motor load.
A drive can power a machine motor, but all other loads on the machine need to have a separate power supply.
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
Released for: Schneider Electric UK





