How to run safety task automatically after power cycle in M580 safety CPU ?
Issue
How to run safety task automatically after power cycle in M580 safety CPU ?

Product line Envirovment
Control Expert, Unity Pro, Modicon M580 safety

Environment
Windows 10 64 bits ,Windows Server 2019 64 bits

Resolution
A warm start causes each process task – including the (MAST, FAST, AUX0, AUX1) tasks – to re-enter its operating state as of the time of the power interruption. By contrast, a warm start causes the SAFE task to enter the STOP state, unless Automatic start in RUN is selected.

snap1.JPG