How can we help you today?

Is it okay not to use the neutral provided in the transfer switch?

Answer:

If the application does not require a neutral, the answer is YES, it is okay not to use / utilize the neutral conductor provided / available in the transfer switch.

ASCO transfer switches will operate and switch between acceptable power sources even without utilizing the provided neutral conductor.  The microprocessor used on the transfer switches monitors the line voltage between the phases only.

Power Sensing Circuits

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center