Can I use a 3-phase transfer switch on a 1-phase system?

Answer: YES.  3-phase transfer switches come with a microprocessor controller that can be set / programmed for 1-phase sensing.

Change the dipswitch settings from 3-phase to 1-phase and connect power cables on phases A and C.

Phase Configuration Dipswitches