Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Does the ATV660 with Full Voltage Bypass have solid state overload protection when in the bypass?

Issue:
Does the Enclosed ATV660 when ordered with Bypass have Solid State Overload?

Product Line:
Altivar and Altivar Process Drive

Environment:
Altivar, Process Drive, ATV660 Enclosed AC Drive

Resolution:
Per the manual, linked below, the ATV660 if ordered with Full Voltage Bypass uses 2 Interlinked TeSys F Contactors, for switching between Drive (AFC) or Bypass (BYP) Mode, which are not Solid State. Also included is a Class 20 separate Overload, as shown on page 43-EN. Please don't hesitate to reply if you have any further questions.

Included with Bypass
• Class 20 overload protection
• Overload Trip (yellow) and Bypass (yellow) pilot lights
• Bypass and isolation contactors with mechanical and electrical interlocking
• Bypass and isolation contactor sequencing provides true motor isolation

ATV660 Manual - https://download.schneider-electric.com/files?p_enDocType=User+guide&p_File_Name=NHA91297_02.pdf&p_Doc_Ref=NHA91297

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings