Which Miniature Circuit Breaker protection devices need to be installed with EVlink Home?
The charging station shall be protected by the following devices:
Circuit Breaker 20A Curve C for each socket 3.7 kW (1P+N)
Circuit Breaker 40A Curve C for each socket 7.4 kW (1P+N)
Circuit Breaker 20A Curve C for each socket 11 kW (3P+N)