Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
How can I make a Modbus register Read Only in a .CSV symbol table file for OFS server?
Issue:
Making a Modbus register Read Only in a .CSV symbol table file for OFS server


Product Line:
OFS Server


Resolution:
In the CSV file you would add a postfix ;R for Read Only in the same cell at the Modbus register, example : 400008;R
see image below
image

As you can see, the registers with the postfix ;R is read only
image

The variables are "read only" only in the OFS Server.
image

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings