How can I make a Modbus register Read Only in a .CSV symbol table file for OFS server?

Issue:
Making a Modbus register Read Only in a .CSV symbol table file for OFS server


Product Line:
OFS Server


Resolution:
In the CSV file you would add a postfix ;R for Read Only in the same cell at the Modbus register, example : 400008;R
see image below
image

As you can see, the registers with the postfix ;R is read only
image

The variables are "read only" only in the OFS Server.
image