Can the Series 300 (with the new Group G controller) be used on a different voltage system?
Answer: Yes, a Series 300 (with the new Group G controller) be used on a different voltage system after some changes are made.
HOWEVER, the following parts below MAY need replacing.
Furthermore, dipswitch settings and voltage jumper positions must be set properly.
A Group G controller has three (3) part numbers and are rated for certain nominal voltages.
A transfer switch coil is also rated for a certain voltage range. For example, a coil assembly can be rated for 190-240V.
So, if a transfer switch came rated at 3-phase 208V and the customer decided to use it on a 1-phase 240V system, they won’t have to replace any part. They just need to change some settings (See Dipswitch tables below).
But, if the transfer switch came rated for 3-phase 480V and they need to use it on a 3-phase 208V system, then they need to replace the Group G controller and the transfer switch coil.



If unsure, contact Technical Support at 1-800-800-ASCO or send an email to technicalsupport@ascopower.com
HOWEVER, the following parts below MAY need replacing.
- Group G controller
- Transfer Switch Coil
Furthermore, dipswitch settings and voltage jumper positions must be set properly.
A Group G controller has three (3) part numbers and are rated for certain nominal voltages.
- PN 894000-001 – 115V and 120V
- PN 894000-002 – 208V, 220V, 230V, 240V, 380V, 400V, 415V, 440V, 460V, and 480V
- PN 894000-003 – 277V, 550V, 575V, and 600V
A transfer switch coil is also rated for a certain voltage range. For example, a coil assembly can be rated for 190-240V.
So, if a transfer switch came rated at 3-phase 208V and the customer decided to use it on a 1-phase 240V system, they won’t have to replace any part. They just need to change some settings (See Dipswitch tables below).
But, if the transfer switch came rated for 3-phase 480V and they need to use it on a 3-phase 208V system, then they need to replace the Group G controller and the transfer switch coil.
If unsure, contact Technical Support at 1-800-800-ASCO or send an email to technicalsupport@ascopower.com
Released for: Schneider Electric UK


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.