AP9520TH Not Showing in the Netbotz 750/755 Web Interface
Issue: AP9520TH Not Showing in the Netbotz 750/755 Interface
Product:
Netbotz 750
Netbotz 755
Environment:
Netbotz 750/755 - Any firmware
AP9520TH – Any Serial Number
Cause:
Connecting an AP9520TH with default DIP switch settings (all switches down. A-link address = 1, refer to below screenshot) will not show on the Netbotz Home page.
The AP9520TH is powered and displays temperature and humidity values.
A repeated error in the log will show.
2022-05-26 09:16:45.030+0800 [Thread-37] ERROR com.se.nb.nativeio.messages.DeviceId:-1 - Enclosure type AP9520TH cannot be on enclosure number 0
2022-05-26 09:16:47.000+0800 [Thread-43] ERROR com.se.nb.nativeio.messages.DeviceId:-1 - Enclosure type AP9520TH cannot be on enclosure number 0
2022-05-26 09:16:50.179+0800 [Thread-43] ERROR com.se.nb.nativeio.messages.DeviceId:-1 - Enclosure type AP9520TH cannot be on enclosure number 0
Resolution:
Start the DIP switch address to #2, refer to the screenshot above or the AP9520TH manual. The AP9520TH sensor should now be available in the Netbotz 750/755 Home page. A restart may be required.
The link address set on the AP9520TH will be minus 1 on the Identifier in the Netbotz web interface.
Example:
The DIP switch setting for this AP9520TH (see first image) is set on Address 2, but the Identifier is shown as 1 on the web interface. The second AP9520TH DIP switch setting is for Address 3, and the identifier is shown as 2.
If your Netbotz 750 is using 8 x AP9520TH, use the DIP switch settings below.
Please note this issue will be resolved in Botzware version 5.3.5
Released for: Schneider Electric UK






Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.