Unable to communicate to Control Expert PLC when programmed with EcoStruxure Operator Terminal Expert
Issue:
Unable to communicate to PLC when linking an XVM / STU file into EcoStruxure Operator Terminal Expert.
Product Line:
EcoStruxure Operator Terminal Expert, Control Expert
Resolution:
In order to properly communicate to a PLC programmed with Control Expert when linking an XVM or STU file, in EcoStruxure Operator Terminal Expert, you must remember to turn on the Data Dictionary feature in Control Expert.
Here is where you can turn on the setting:
Released for:Schneider Electric UK