Do the TM3AI2H, TM3AI4, TM3AI8 or TM3TI4 modules require an external loop power supply or do the modules provide it for the 4-20mA current loops ?

The TM3AI2H, TM3AI4, TM3AI8 or TM3TI4 require an external loop power supply for their 4-20mA current loops. The module does not provide it. Here is an example

wiring diagram


If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.