Can the old ATV71 chokes be used with the modern ATV600 and ATV900 process drives?

No, ATV61/ATV71 chokes should not be repurposed for ATV600/ATV900 drives.

FeatureATV61/ATV71 Motor Choke (VW3A5103)ATV600/ATV900 dv/dt Filter (VW3A5304)
Intended Drive RangeAltivar 61 / Altivar 71Altivar Process 600 / Altivar Process 900
Compatibility with ATV600/900Not recommendedRecommended
Circuit TypeL (Inductor only)LC (Inductor + Capacitor)
Inductance80 µH180 µH
CapacitanceN/A0.087 µF
Maximum Cable Length (Unshielded)200 m500 m
Maximum dv/dt750 V/µs1000 V/µs
PerformanceOlder technologyMore efficient design
Schneider Electric RecommendationDo not reuse with ATV600/900 drivesUse for ATV600/900 applications with longer motor cables
Validation Testing on ATV630D15N4Not testedFully documented solution
Warranty/Performance AssuranceCannot be assuredSupported and recommended

Key Points

  • The VW3A5103 (ATV61/ATV71) and VW3A5304 (ATV600/ATV900) are fundamentally different products.
  • For an ATV630D15N4 with long motor cable runs (e.g., 120 m SWA cable), Schneider Electric recommends the VW3A5304 dv/dt filter to reduce overvoltage and high dv/dt at the motor terminals.
  • Using the older choke with an ATV600/900 drive is undocumented and untested, so correct operation cannot be guaranteed.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center