My HMIST6 is not booting, is there a way to recover it?

Issue

The HMIST6 does not boot, it stays on a loading screen with a blue circle.

Product Line

HMIST6 series, HMISTM6 series and HMISTO series.

Environment

HMI programmed with EcoStruxure Operator Terminal Expert 3.2 SP2 and newer.

Cause

In some cases, when a display unit failed to accept the project in a transfer operation, the HMI cannot boot and Recovery Mode must be opened.

Resolution

Here are the steps to access Recovery Mode:

1. Power off the HMI.

2. Power on the HMI.

3. While it is booting and the screen shows the green loading bar, touch and hold the bottom-left corner or bottom-right corner of the display until a dialog box asking "Do you want to enter recovery mode?" appears. It takes about 10 seconds for the dialog box to show up.

Recovery Mode Dialog Box

3. Click [Yes] to enter recovery mode.

4. Transfer the project, depending on your transfer method.

This recovery process was introduced on EOTE v3.2 SP2. It will not work with HMIs programmed with older versions of EcoStruxure Operator Terminal Expert.

Please contact technical support if further assistance is needed after trying this procedure.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center