Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Why can't I see the Backward Compatibility tab in SoSafe Bus Configurator tool, even when backwards compatibility is enabled?

If you are clicking to enable backward compatibility in the settings tab, but not seeing the tab show up next to parameters, then you must first enable some settings in the configuration file entitled "conf".

To show the backward compatibility tab, "I/O_Select" option in the configuration file must be set to 1. To enable full functionality of the tab, you may also make sure that "I/O_Modulari" is set to 1.

Configuration file options for Sosafe Bus Configurator tool

To do this, first find the file folder. This is easily done by right-clicking on the desktop shortcut for bus configurator, and clicking open file location. Unless downloaded to specific location, this should be in your main drive under programme files and then: Schneider Electric\SoSafe Configurable\Bus Configurator.

Once here, open the file named 'conf'. You may now change values from '0' to '1' against the relevant options.

There are also options for debug and log.txt in this file.

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings