Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Tracking DB Lock Usage in Geo SCADA
DB Lock Usage could be tracked and historized. This is helpful to visualize the utilization of database locks across the system over time.
Several OPC properties related to DB Lock Usage are located here:
  • PerformanceStats.LUSPercLockAcquired
  • PerformanceStats.LUSPercLockAcquiredTime
  • PerformanceStats.LUSAlarmed

The LUSPercLockAcquired OPC property is the one we are interested in. Please create an Analog Calculation point and configure it to the following settings:
Calculation Point Settings
Calculation Point Settings
Make sure the Historic aggregate is enabled on the calculation point.
The DB Lock Usage can now be tracked:
Trending DB Lock Usage
Viewing DB Lock Usage in Historic List

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings