How can we help you today?

Why are the REAL data type variables data not showing correctly in Vijeo Designer when communicating to a M340 PLC?

Issue:
REAL data type variables data not showing correctly in Vijeo Designer when communicating to a M340 PLC.


Product Line:
Vijeo Designer, M340


Resolution:
The REAL data type variables may not show correctly due to word order not set correctly in Vijeo Designer. When the HMI is communicating to an M340 PLC the double word order must be "Low word first". To change the word order, expand the I/O manager in the navigator and double click on the equipment.

imagew

Ensure that the Double Word word order is set to "Low word first"
image2

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center