Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
		
How can we help you today?
Vijeo Designer, how to have the HMI display a specific page when it wakes up and the backlight turns ON?

Issue:

Need to have a specific panel or page to be displayed on the HMI when it wakes up and the backlight turns ON.

Product Line:

Vijeo Designer, Magelis HMI and Harmony HMI.

Resolution:

The information for the HMI backlight status and control can be found in the Vijeo Designer Help, section 6.7.1:

Help section _BackLight

_Backlight.Control

_BackLight.Status

To have the HMI go to a specific panel when it wakes up and the backlight comes ON, follow these steps:

Set the Backlight - Sleep after property of the target under the Hardware tab.

Hardware - BackLight - Sleep After property

Then configure a Conditional Action using the trigger variable "_BackLight.Status", trigger "On Data Change" and click Next.

Action on _BackLight.Status

Add a Decision operation on the "_BackLight.Status" system variable, that when true, will do a Change Panel action to the desired panel.

Decision on _BackLight.Status

Then, click the Finish button. Make sure the action is added correctly.

Action configured

See the Test_Backlight.vdz example project.

Schneider Electric UK

Attachment(s)
Test_Backlight.vdz [29.32 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings