Ecostruxure Automation Expert[22.0]: Deployment time out error

This document explains on how to resolve Deployment timeout error appearing when a user tries to deploy a project to a M580DPAC controller.

For larger projects, User sometimes might experience "Deploy Timeout error" as shown below.

timeout

For resolving this issue, User needs to tune the ECORT Plugin Settings which can be accessed as shown below.


plugin settings

The Upload timeout is 60 seconds by default and needs to be increased if Deploy timeout is appearing frequently. After modifying the setting, compile the project and deploy the project.