How to connect my Control Expert client to the server ?
Before starting Control Expert Topology Manager (TM) on the client side, please follow these steps:
- Close TM on the server side.
- Open the Server Configuration.
- In the Listening Connections tab, update the Listening IP address:
- Either select the Ethernet card used to communicate with the client PC,
- Or enter 0.0.0.0 to listen on all Ethernet interfaces.
- For example: IP = 192.168.189.1, Port = 19950.
You should now be able to connect to the server successfully.
Released for: Schneider Electric UK
Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.