Why do I get the error message " Controller cannot change operating mode at this stage. Verify that its application is appropriate and the Run/Stop switch or input is in the correct position." when I try to start the controller in simulation mode?
Issue:
Error message "Controller cannot change operating mode at this stage. Verify that its application is appropriate and the Run/Stop switch or input is in the correct position. If the controller is in HALTED state, you must initialize it" when starting the controller in simulation mode
Product Line:
M221, EcoStruxure Machine Expert Basic
Resolution:
The error message "Controller cannot change operating mode at this stage. Verify that its application is appropriate and the Run/Stop switch or input is in the correct position. If the controller is in HALTED state, you must initialize it" is cause by having a run/stop input configured in the EcoStruxure Machine Expert Basic program. You must uncheck the run/stop input in order to start/Run the PLC in simulation mode.

Error message "Controller cannot change operating mode at this stage. Verify that its application is appropriate and the Run/Stop switch or input is in the correct position. If the controller is in HALTED state, you must initialize it" when starting the controller in simulation mode
Product Line:
M221, EcoStruxure Machine Expert Basic
Resolution:
The error message "Controller cannot change operating mode at this stage. Verify that its application is appropriate and the Run/Stop switch or input is in the correct position. If the controller is in HALTED state, you must initialize it" is cause by having a run/stop input configured in the EcoStruxure Machine Expert Basic program. You must uncheck the run/stop input in order to start/Run the PLC in simulation mode.
Released for: Schneider Electric UK


Need help?
Product Selector
Quickly and easily find the right products and accessories for your applications.
Get a Quote
Start your sales inquiry online and an expert will connect with you.
Where to buy?
Easily find the nearest Schneider Electric distributor in your location.
Help Centre
Find support resources for all your needs, in one place.