Unable to access NMC3 via HTTPS using Chrome - ERR_CERT_INVALID

Problem:
Users are unable to access an NMC3 with a self-signed certificate via HTTPS using recent versions of the Google Chrome browser

Environment:
UPS Network Management Card 3 - AP9640/41/43
Devices that use an embedded NMC3, including but not limited to PDU (2022+ model AP8xxx, APDU9xxx), ATS (AP44xxA), and Smart-UPS/Symmetra UPS systems

Cause:
A recent Chrome update is blocking the self-signed certificate ECC certificate that is used by default on an NMC3.

Resolution:
This will be addressed in a future version of firmware, and this article will be updated when a fix version is available.

Please note that this issue is fixed from firmware rev. 2.4, so updating firmware should be fist step in the troubleshooting process.

Secondary workarounds are:

  • Use a different browser
  • Use an older version of Chrome
  • Delete the ECC self-signed certificate on the NMC and generate an RSA cert. The commands can be performed via the CLI:
    • apc>ssl key -d
    • apc>ssl key -rsa [1024|2048|4096]
  • Use the CLI Security Wizard and a 3rd party certificate authority to create a signed certificate


Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center