How can I upgrade my SCADAPack x70 devices' Realflo licence?
  • Contact your Local Representative and purchase the required upgrade license.
  • Our customer support team will e-mail you with the upgrade License that was purchased.
  • Saved this License in your desktop folder.
  • Create a new project using RemoteConnect.
  • Go online with the device.
  • Under My Network, right-click on SCADAPack x70 Controller Settings -DeviceDTM and select Additional Functions > Apply License to Device
Apply License
  • in the Apply License to Device dialog, click Browse to navigate to the location where the license file is stored. The license file has a .lic extension.
  • In the open dialog, select the license file, then click Open
  • In the Apply License to Device dialog, click Ok. A restart of the device is required to activate license options after the license has been successfully applied to it.
  • In the pop-up dialog, click Yes to confirm.
apply license 2
  • Verify the license's modifications. Under Online Diags>Licensing then hit refresh button.
apply license 3

Schneider Electric UK

Explore more
Product:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Product:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings