How can we help you today?

How to successfully open a stu app whose opening with CEV15.2 displays an error message?

Issue
After retrieving the app sta with CEV15.2 from the PLC, changes are made to the same app and then saved in stu. Then opening this app will display the following error message:
Error on when opening the project file
Product Line
M580

Environment
Windows 10 Pro, Control Expert V15.2

Resolution
  • The workaround we provide is as follows :
  • Open the app in sta format,
  • Export the project in zef format
  • Close the .sta and open the .zef and make a save in stu format then close this application in zef format
  • Open the application in .stu format and normally the problem before now disappears

Schneider Electric UK

Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center