How can we help you today?

MTZ Maximum Zs figures for 0.4 seconds disconnection

The Zs for MTZ used to be done from the settings on the Micrologic X and using the following formula - Zs = 218.5/In x Ir x Isd x 1.1

Where - 218.5 is the 230 voltage to earth multiplied by the Cmin factor 0.95 divided by - In = Device rating x Ir = Long time dial setting x Isd = short time setting x 1.1 a 10% tolerance for the Isd short time setting.

Now it can be done easily by entering your figures into the attached (Related Tab) Excel file.
A 1000A example has been entered on Line 5.

Schneider Electric UK

Attachment(s)
MTZ Zs 0.4s spreadsheet.xlsx [12.34 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • General Terms of Business
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings
  • Preference Center