MTZ Maximum Zs figures for 0.4 seconds disconnection

The Zs for MTZ used to be done from the settings on the Micrologic X and using the following formula - Zs = 218.5/In x Ir x Isd x 1.1

Where - 218.5 is the 230 voltage to earth multiplied by the Cmin factor 0.95 divided by - In = Device rating x Ir = Long time dial setting x Isd = short time setting x 1.1 a 10% tolerance for the Isd short time setting.

Now it can be done easily by entering your figures into the attached (Related Tab) Excel file.
A 1000A example has been entered on Line 5.

Schneider Electric UK

Attachment(s)
MTZ Zs 0.4s spreadsheet.xlsx [12.34 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:

Need help?

Need help?

Product Selector

Product Selector

Quickly and easily find the right products and accessories for your applications.

Get a Quote

Get a Quote

Start your sales inquiry online and an expert will connect with you.

Where to buy?

Where to buy?

Easily find the nearest Schneider Electric distributor in your location.

Help Centre

Help Centre

Find support resources for all your needs, in one place.

  • Products Documentation
  • Software Downloads
  • Product Selector
  • Product Substitution and Replacement
  • Help and contact centre
  • Where to buy
  • Get a Quote
  • Find our Offices
  • Schneider Electric Community
  • Careers
  • Company Profile
  • Report a misconduct
  • Accessibility
  • Newsroom
  • Investors
  • EcoStruxure
  • Job Search
  • Blog
  • Privacy Policy
  • Cookie Notice
  • Terms of use
  • Change your cookie settings